DocumentCode :
1236212
Title :
Experimental study of response of power distribution lines to direct lightning hits
Author :
Yokoyama, S. ; Asakawa, A.
Author_Institution :
Central Res. Inst. of Electr. Power Ind., Tokyo, Japan
Volume :
4
Issue :
4
fYear :
1989
fDate :
10/1/1989 12:00:00 AM
Firstpage :
2242
Lastpage :
2248
Abstract :
In order to clarify the response of overhead distribution lines to direct lightning hits, experimental facilities were installed at the UHV Shiobara Testing Laboratory of CRIEPI. A lightning impulse current with a crest value of 18 kA and a waveform of (2/11) μs was generated through the impulse current generator with a high internal resistance of 400 Ω. This impulse current is not easily affected by the conditions of a distribution line side. Protective effects of surge arresters and an overhead ground wire against direct strokes to the pole of a distribution line were clarified experimentally. Experimental results showed a better protective effect than earlier calculated results. Overvoltages between a line conductor and the earth are inclined to have a short wavetail. The 50% flashover voltage of an insulator against overvoltages with a short wavetail is higher than that against overvoltages with a standard wavetail
Keywords :
distribution networks; flashover; lightning; power overhead lines; surge protection; 18 kA; 400 ohm; UHV Shiobara Testing Laboratory of CRIEPI; direct lightning hits; flashover voltage; impulse current generator; lightning impulse current; line conductor; overhead distribution lines; overhead ground wire; overvoltage; surge arresters; Arresters; Conductors; Earth; Flashover; Laboratories; Lightning; Power distribution lines; Surge protection; Testing; Wire;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/61.35653
Filename :
35653
Link To Document :
بازگشت