Staged Fault and Laboratory Tests on a Cable Pair Protection System Designed to Serve Power Stations
Author
Geer, Eugene W., Jr. ; Whatmough, J. Read
Author_Institution
Bell Labs., Whippany, NJ, USA
Volume
22
Issue
2
fYear
1974
fDate
2/1/1974 12:00:00 AM
Firstpage
193
Lastpage
199
Abstract
Cable pairs entering power stations may be subjected to ground potential rise (GPR) and/or induction of several thousand volts during power system faults. A cable protection system designed to give a high degree of reliability is described, and the results of staged fault and laboratory tests are discussed. An analysis of neutralizing transformer transient performance shows how the transformer´s behavior during fault conditions is determined by its volt-time capability.
Keywords
Power system communications; Protective relaying; Telephone cables; Ground penetrating radar; Laboratories; Performance analysis; Power cables; Power generation; Power system faults; Power system protection; Power system reliability; Power system transients; System testing;