Title :
Generator protection and CT-saturation problems and solutions
Author :
Kasztenny, Bogdan ; Finney, Dale
Author_Institution :
Gen. Electr., Markham, Ont., Canada
Abstract :
This paper presents a new generator relay design, stator differential function in particular, coping with extreme cases of current transformer (CT) saturation: both ac saturation under large currents and/or residual flux; and dc saturation under low currents but large and long-lasting dc components. The algorithm is a subcycle algorithm with fastest times reaching half a cycle including overall response of the relay hardware. Analysis of the response of a traditional differential function under CT saturation is included to provide setting guidelines for legacy relays.
Keywords :
current transformers; electric generators; machine protection; power transformer protection; relay protection; stators; current transformer-saturation problems; dc saturation; generator protection; generator relay design; residual flux; stator differential function; subcycle algorithm; AC generators; Circuit faults; Current transformers; DC generators; Fault currents; Hardware; Protection; Protective relaying; Relays; Stators; Current transformers (CTs); directional comparison; generator protection; saturation; saturation detection; spurious differential current; stator differential protection;
Journal_Title :
Industry Applications, IEEE Transactions on
DOI :
10.1109/TIA.2005.858298