DocumentCode :
1247082
Title :
Estimating the remaining service life of asphalt-mica stator insulation
Author :
Timperley, J.E. ; Michalec, J.R.
Author_Institution :
American Electr. Power Service Corp., Columbus, OH, USA
Volume :
9
Issue :
4
fYear :
1994
fDate :
12/1/1994 12:00:00 AM
Firstpage :
686
Lastpage :
694
Abstract :
Synchronous generators were manufactured with asphalt bonded, mica flake insulation from 1917 to the 1950s. There is a large fleet, perhaps two thousand, of these machines still in service today. This paper presents the results of a well documented series of field tests, many to failure, on 20 asphalt-mica insulated fossil fuel and hydroelectric synchronous generators on the American Electric Power system and laboratory tests on over 30 spare asphalt-mica stator bars and coils at AEP´s Dolan Laboratory. The paper clearly shows that a straightforward AC overpotential test and a simple graphical evaluation and analysis can be used to confidently determine the remaining service life of asphalt bonded, mica flake insulated synchronous generators that have been well maintained and operated within design limits
Keywords :
electric breakdown; electric strength; insulation testing; life testing; machine insulation; machine testing; mica; stators; synchronous generators; AC overpotential test; asphalt-mica stator insulation; bars; coils; design limits; failure; field tests; fossil fuel generation; graphical evaluation; hydroelectric generation; laboratory tests; service life; synchronous generators; Asphalt; Bonding; Dielectrics and electrical insulation; Fossil fuels; Laboratories; Life estimation; Manufacturing; Stators; Synchronous generators; System testing;
fLanguage :
English
Journal_Title :
Energy Conversion, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8969
Type :
jour
DOI :
10.1109/60.368340
Filename :
368340
Link To Document :
بازگشت