• DocumentCode
    1247082
  • Title

    Estimating the remaining service life of asphalt-mica stator insulation

  • Author

    Timperley, J.E. ; Michalec, J.R.

  • Author_Institution
    American Electr. Power Service Corp., Columbus, OH, USA
  • Volume
    9
  • Issue
    4
  • fYear
    1994
  • fDate
    12/1/1994 12:00:00 AM
  • Firstpage
    686
  • Lastpage
    694
  • Abstract
    Synchronous generators were manufactured with asphalt bonded, mica flake insulation from 1917 to the 1950s. There is a large fleet, perhaps two thousand, of these machines still in service today. This paper presents the results of a well documented series of field tests, many to failure, on 20 asphalt-mica insulated fossil fuel and hydroelectric synchronous generators on the American Electric Power system and laboratory tests on over 30 spare asphalt-mica stator bars and coils at AEP´s Dolan Laboratory. The paper clearly shows that a straightforward AC overpotential test and a simple graphical evaluation and analysis can be used to confidently determine the remaining service life of asphalt bonded, mica flake insulated synchronous generators that have been well maintained and operated within design limits
  • Keywords
    electric breakdown; electric strength; insulation testing; life testing; machine insulation; machine testing; mica; stators; synchronous generators; AC overpotential test; asphalt-mica stator insulation; bars; coils; design limits; failure; field tests; fossil fuel generation; graphical evaluation; hydroelectric generation; laboratory tests; service life; synchronous generators; Asphalt; Bonding; Dielectrics and electrical insulation; Fossil fuels; Laboratories; Life estimation; Manufacturing; Stators; Synchronous generators; System testing;
  • fLanguage
    English
  • Journal_Title
    Energy Conversion, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8969
  • Type

    jour

  • DOI
    10.1109/60.368340
  • Filename
    368340