DocumentCode :
1247183
Title :
Intelligent reclosing for overdutied breakers
Author :
Apostolo, A.P. ; Bronfeld, J.D. ; Feltis, M.W.
Author_Institution :
New York State Electr. & Gas Corp., Binghamton, NY, USA
Volume :
10
Issue :
1
fYear :
1995
fDate :
1/1/1995 12:00:00 AM
Firstpage :
153
Lastpage :
158
Abstract :
The increase in fault current magnitudes above the derated breaker interrupting capability requires the use of circuit breaker replacement, current limiting devices, changes in system configuration, etc. All the above solutions to the overdutied breaker problem are very expensive. This paper demonstrates that by applying a combination of breaker trip with fault current control and adjusting the number of reclosing shots as a function of the fault current magnitude, breakers overdutied by fault currents between the derated and 100% of the breaker interrupting capability do not need replacement. This approach was applied in New York State Electric and Gas (NYSEG)´s system for about 30 overdutied breakers
Keywords :
circuit breakers; current limiters; intelligent control; microcomputer applications; power system control; power system protection; power system relaying; relay protection; breaker trip; derated breaker interrupting capability; fault current control; fault current magnitude; intelligent reclosing; overdutied breakers; power systems; reclosing shots; Circuit faults; Current limiters; Fault currents; IEEE members; Logic devices; Programmable logic arrays; Programmable logic devices; Relays; Substations; Transformers;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/61.368403
Filename :
368403
Link To Document :
بازگشت