DocumentCode
1247209
Title
Evaluation of 230 kV HPFF pipe-type cable with wrinkled and creased insulating tapes
Author
Seman, G.W. ; Katz, C. ; Pancholi, S.V.
Author_Institution
Cable Technol. Lab. Inc., New Brunswick, NJ, USA
Volume
10
Issue
1
fYear
1995
fDate
1/1/1995 12:00:00 AM
Firstpage
53
Lastpage
61
Abstract
Severe collapse wrinkles and circumferential creases were discovered in the cellulose paper insulating tapes of a newly installed HPFF pipe-type cable during splicing and terminating. An evaluation program was developed to assess the electrical and mechanical integrity of the cable having wrinkled and creased insulating tapes. The test results indicated that the cable would perform satisfactorily in service
Keywords
cable jointing; insulating oils; insulation testing; paper; power cable insulation; power cable testing; power cables; 230 kV; HPFF pipe-type cable; cable splicing; cable termination; cellulose paper insulating tapes; circumferential creases; collapse wrinkles; creased insulating tapes; electrical integrity; high pressure fluid filled cable; mechanical integrity; wrinkled insulating tapes; Cable insulation; Dielectrics and electrical insulation; Laboratories; Manufacturing; Mechanical cables; Performance evaluation; Power cable insulation; Power cables; Splicing; Testing;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/61.368416
Filename
368416
Link To Document