• DocumentCode
    1248261
  • Title

    Development and laboratory testing of a 138 kV PPP-insulated joint for commercial application

  • Author

    Walldorf, S.P. ; Chu, H. ; ElBadaly, H.

  • Author_Institution
    MAC Products Inc., Kearny, NJ, USA
  • Volume
    5
  • Issue
    2
  • fYear
    1990
  • fDate
    4/1/1990 12:00:00 AM
  • Firstpage
    799
  • Lastpage
    805
  • Abstract
    The design, development, and laboratory testing of a PPP (paper/polypropylene/paper)-insulated joint for commercial application on 1389 kV PPP-insulated cable are presented. The design approach taken is conservative and addresses the typical variations in field conditions and in skill and workmanship of the splicing. Joint construction details, including choice of connector, taping structure, and joint mechanical reinforcement, are discussed. The test criteria are described, and results are presented
  • Keywords
    cable insulation; cable jointing; cable testing; organic insulating materials; power cables; 138 kV; cable jointing; connector; design; development; mechanical reinforcement; organic insulating materials; paper/polypropylene/paper; power cable testing; splicing; taping; Breakdown voltage; Conductors; Connectors; Copper; Dielectric breakdown; Dielectrics and electrical insulation; Impulse testing; Laminates; Splicing; Stress;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.53086
  • Filename
    53086