• DocumentCode
    1248459
  • Title

    Modeling and analysis of URD cable systems

  • Author

    MelioPoulos, A. P Sakis ; Masson, Jean-Francois

  • Author_Institution
    Sch. of Electr. Eng., Georgia Inst. of Technol., Atlanta, GA, USA
  • Volume
    5
  • Issue
    2
  • fYear
    1990
  • fDate
    4/1/1990 12:00:00 AM
  • Firstpage
    806
  • Lastpage
    815
  • Abstract
    A method for modeling URD cables with explicit grounding representation is presented. The model accurately represents the skin effect in the cable conductor and shield, as well as in the soil and multiple grounds connected to the cable shield. The method is capable of representing insulated cables, semiconducting jackets, or bare concentric neutral cables. The accuracy of the model is validated by comparison with closed-form solutions of simple cable arrangements. The URD cable model has been integrated into EPRI´s SMECC program, a program designed to analyze the ground potential rise of grounding structures. The overall model is also useful for analysis of effects due to loss of cable neutral. Typical results illustrate the effectiveness of URD cables in reducing ground potential rise and effects of loss of neutral
  • Keywords
    digital simulation; earthing; power cables; power engineering computing; underground cables; underground residential distribution systems; URD; concentric neutral; digital simulation; earthing; ground potential rise; grounding; modeling; power cables; power engineering computing; skin effect; soil; underground residential distribution systems; Cable insulation; Cable shielding; Conductors; Earth; Grounding; Power cable insulation; Power cables; Power system modeling; Soil; Surface impedance;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.53087
  • Filename
    53087