DocumentCode
1248971
Title
Steady State Stability and Subsynchronous Resonance of Shunt Capacitor Compensated AC Transmission Lines
Author
Ooi, Boon-Teck
Author_Institution
Department of Electrical Engineering, McGill University, Montreal, Canada
Issue
9
fYear
1982
Firstpage
45
Lastpage
45
Abstract
It is shown that the fifth quadrant operation of the shunt capacitor compensated transmission line is dynamically stable, both with and without the voltage stabilizer. Unfortunately, before the economic advantages can be exploited, it is necessary to overcome the problem of subsynchronous resonance which is shown here to be unavoidable when operating beyond the second quadrant. This paper arrives at these conclusions through proofs of the operating limits for subsynchronous resonance and proofs of the stabilty limits.
Keywords
AC generators; Capacitors; Character generation; Power transmission lines; Reactive power; Resonance; Shunt (electrical); Stability analysis; Steady-state; Transmission lines;
fLanguage
English
Journal_Title
Power Engineering Review, IEEE
Publisher
ieee
ISSN
0272-1724
Type
jour
DOI
10.1109/MPER.1982.5519483
Filename
5519483
Link To Document