DocumentCode
1249538
Title
Accurate fault location technique for power transmission lines
Author
Johns, A.T. ; Jamali, S.
Author_Institution
City Univ., London, UK
Volume
137
Issue
6
fYear
1990
fDate
11/1/1990 12:00:00 AM
Firstpage
395
Lastpage
402
Abstract
The authors describe a very accurate fault location technique which uses post-fault voltage and current derived at both line ends. Fault location is independent of fault resistance and the method does not require any knowledge of source impedance. It maintains high accuracy for untransposed lines and no fault type identification is required. The authors present the theory of the technique and the results of simulation studies to determine its performance
Keywords
fault location; power transmission lines; fault location; post-fault current; post-fault voltage; power transmission lines; untransposed lines;
fLanguage
English
Journal_Title
Generation, Transmission and Distribution, IEE Proceedings C
Publisher
iet
ISSN
0143-7046
Type
jour
Filename
62475