DocumentCode
1249861
Title
Reset Characteristics of Automatic Resetting Type Fault Indicators on Three-Phase URD Systems
Author
Thomas, Harry ; Kalmuck, John
Author_Institution
Long Island Lighting Company, Hicksville, NY
Issue
8
fYear
1982
Firstpage
19
Lastpage
20
Abstract
The need for reliable fault indication in industrial parks has never been greater than it is today. For the most part, these areas are serviced by three-phase multilegged core padmount transformers. If single-phasing occurs, a voltage induced in the open leg could cause automatic resetting type fault indicators to incorrectly reset as a result. This paper deals with such a situation and its solution. Studies and tests by Long Island Lighting and RTE determined the magnitude of the incident, its effect on associated equipment, and what new product application information resulted.
Keywords
Circuit faults; Circuit testing; Electrical equipment industry; Fuses; Power system reliability; Power system restoration; Power system transients; Protection; Transformers; Voltage;
fLanguage
English
Journal_Title
Power Engineering Review, IEEE
Publisher
ieee
ISSN
0272-1724
Type
jour
DOI
10.1109/MPER.1982.5519724
Filename
5519724
Link To Document