On-line utility tie power factor control
Author :
Burrow, David ; Wu, Alex
Author_Institution :
Union Camp Corp., Savannah, GA, USA
Volume :
3
Issue :
4
fYear :
1997
Firstpage :
43
Lastpage :
47
Abstract :
Large industrial operations with internal electrical generation capabilities and parallel utility ties have always worked to control watt and VAr flows across their tie lines. In today´s economic climate, the ability to control tie line operation can significantly impact a facility´s bottom line. In a power system expansion, Union Camp Corporation´s Savannah pulp and paper mill installed a tie line power factor control system that has proven to be reliable and effective. It uses load tap changers on two pairs of utility tie transformers to maintain control within the guidelines of the utility contract. It is implemented by a programmable logic controller (PLC) and other nonproprietary hardware. An analysis of this project illustrates how this scheme can be implemented on simple or complex power systems
Keywords :
industrial power systems; paper industry; power factor correction; power system control; power transformers; programmable controllers; reactive power control; Savannah pulp and paper mill; Union Camp Corporation; VAr flow control; economic climate; industrial operations; internal electrical generation capabilities; load tap changers; parallel utility ties; power system expansion; programmable logic controller; utility tie power factor control; utility tie transformers; watt flow control; Electrical equipment industry; Industrial control; Industrial power systems; Power generation economics; Power system control; Power system economics; Power system reliability; Power systems; Programmable control; Reactive power;
fLanguage :
English
Journal_Title :
Industry Applications Magazine, IEEE
Publisher :
ieee
ISSN :
1077-2618
Type :
jour
DOI :
10.1109/2943.590679
Filename :
590679
Link To Document :
بازگشت