  • Abstract
    Single and multiple rod gaps are used for the overvoltage protection of various power system apparatus. These are mostly located outdoors and are subjected to particulate contamination in desert lands. This paper discusses the influence of pollution on the breakdown voltage and breakdown time of protective air gaps. The rod radius and its end profile are changed to find the configuration which is least affected by pollution. In addition, practical protective gaps used across transformer bushings are tested to check their performance in clean and polluted conditions. It is found that such pollution drastically changes the gaps performance. Specific recommendations are made regarding the choice of suitable protective rod gap configuration for arid regions
  • Keywords
    air gaps; dust; electric breakdown; insulation co-ordination; overvoltage protection; power apparatus; power system protection; switchgear testing; breakdown time; breakdown voltage; desert lands; dust particles; lightning impulses; medium voltage networks; particulate contamination; pollution effects; power system apparatus; protective air gaps; protective rod gaps; transformer bushings; Breakdown voltage; Insulators; Intelligent networks; Lightning; Medium voltage; Pollution; Power transformer insulation; Protection; Storms; Voltage control;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.796223
  • Filename
    796223