DocumentCode
1252048
Title
Overvoltages due to switching off an unloaded transformer with a vacuum circuit breaker
Author
Popov, Marjan ; Acha, Enrique
Author_Institution
Univ. St. Cyril & Methodious, Skopje, Macedonia
Volume
14
Issue
4
fYear
1999
fDate
10/1/1999 12:00:00 AM
Firstpage
1317
Lastpage
1326
Abstract
When a vacuum breaker is used to disconnect an unloaded transformer, high overvoltages may result on the secondary side. The phenomena of current chopping and multiple reignitions after contact opening, shortly before current zero, play a significant role in generating these overvoltages, Furthermore, the transient recovery voltage (TRV) is also influenced by virtual current chopping which may lead to fast interruptions and reignitions. The paper reports on a vacuum breaker model implemented in the ATP-EMTP program. Simulations have been performed to determine overvoltages generated by the vacuum breaker, before and after suppression. Network elements were simulated by simplified models of limited complexity
Keywords
overvoltage protection; power system analysis computing; power system protection; power transformers; switching; vacuum circuit breakers; ATP-EMTP; computer simulation; current chopping; disconnection; interruptions; multiple reignitions; secondary side overvoltages; transient recovery voltage; unloaded transformer switching; vacuum circuit breaker; Capacitance; Circuit breakers; Circuit simulation; Furnaces; Large Hadron Collider; Surges; Switchgear; Switching circuits; Vacuum arcs; Voltage;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/61.796224
Filename
796224
Link To Document