• DocumentCode
    1252048
  • Title

    Overvoltages due to switching off an unloaded transformer with a vacuum circuit breaker

  • Author

    Popov, Marjan ; Acha, Enrique

  • Author_Institution
    Univ. St. Cyril & Methodious, Skopje, Macedonia
  • Volume
    14
  • Issue
    4
  • fYear
    1999
  • fDate
    10/1/1999 12:00:00 AM
  • Firstpage
    1317
  • Lastpage
    1326
  • Abstract
    When a vacuum breaker is used to disconnect an unloaded transformer, high overvoltages may result on the secondary side. The phenomena of current chopping and multiple reignitions after contact opening, shortly before current zero, play a significant role in generating these overvoltages, Furthermore, the transient recovery voltage (TRV) is also influenced by virtual current chopping which may lead to fast interruptions and reignitions. The paper reports on a vacuum breaker model implemented in the ATP-EMTP program. Simulations have been performed to determine overvoltages generated by the vacuum breaker, before and after suppression. Network elements were simulated by simplified models of limited complexity
  • Keywords
    overvoltage protection; power system analysis computing; power system protection; power transformers; switching; vacuum circuit breakers; ATP-EMTP; computer simulation; current chopping; disconnection; interruptions; multiple reignitions; secondary side overvoltages; transient recovery voltage; unloaded transformer switching; vacuum circuit breaker; Capacitance; Circuit breakers; Circuit simulation; Furnaces; Large Hadron Collider; Surges; Switchgear; Switching circuits; Vacuum arcs; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.796224
  • Filename
    796224