• DocumentCode
    1252139
  • Title

    Corona caused deterioration of ADSS fiber-optic cables on high voltage lines

  • Author

    Karady, George G. ; Besztercey, Gynla ; Tuominen, M.W.

  • Author_Institution
    Dept. of Electr. Eng., Arizona State Univ., Tempe, AZ, USA
  • Volume
    14
  • Issue
    4
  • fYear
    1999
  • fDate
    10/1/1999 12:00:00 AM
  • Firstpage
    1438
  • Lastpage
    1447
  • Abstract
    Deterioration of an ADSS (all dielectric self-supporting) fiber optic cable jacket material has been reported near the tips of armor rod assemblies installed on high voltage transmission lines. Field observations and laboratory tests revealed that corona can exist on the tips of the armor rod. Electric field analyses reported herein reveal that the tip surface gradients are high enough to produce corona. Field conditions have been duplicated in a high voltage test chamber and jacket damage has been observed near generated corona. The deterioration mechanism is identified and jacket life expectancy is estimated. Different mitigation techniques are suggested
  • Keywords
    cable insulation; cable sheathing; cable testing; corona; insulation testing; optical cables; power transmission lines; HV power transmission lines; all-dielectric self-supporting fiber optic cable; armor rod assembly tips; corona; deterioration mechanism; electric field analyses; field observations; high voltage test chamber; jacket damage; jacket life expectancy; jacket material deterioration; laboratory tests; mitigation techniques; tip surface gradients; Assembly; Corona; Dielectric materials; Laboratories; Optical fiber cables; Optical fiber testing; Optical fibers; Optical materials; Transmission lines; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.796238
  • Filename
    796238