DocumentCode
1252175
Title
Application and experience with a 15 kV static transfer switch
Author
Jipping, Jon E. ; Carter, William E.
Author_Institution
Detroit Edison Co., MI, USA
Volume
14
Issue
4
fYear
1999
fDate
10/1/1999 12:00:00 AM
Firstpage
1477
Lastpage
1481
Abstract
In an effort to dramatically improve reliability to a sensitive customer, Detroit Edison, a DTE Energy Company, installed a 15 kV static transfer switch (STS). This paper presents the background on the electrical system disturbances which had a negative impact on an automotive components plant served by Detroit Edison. Previous steps taken, the studies performed, planning considerations, and the most recent actions taken to resolve the reliability issues are described. In addition, the performance of the STS during its first year of service is detailed. This application demonstrates that if there is adequate isolation of the two sources for the STS, it can avoid disturbances from voltage sags and outages, thus greatly improving overall reliability for the customer
Keywords
power supply quality; power system faults; power system protection; power system reliability; switchgear; 15 kV; customer reliability improvement; outages; planning considerations; power system disturbances; reliability issues; static transfer switch; voltage sags; Assembly; Automobiles; Automotive components; Feeds; Manufacturing processes; Power quality; Power system protection; Sociotechnical systems; Substation protection; Switches;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/61.796243
Filename
796243
Link To Document