DocumentCode :
1255080
Title :
Fundamental studies on vacuum circuit breaker arc quenching limits with a synthetic test circuit
Author :
Betz, Thomas ; Koenig, Dieter
Author_Institution :
High Voltage Lab., Darmstadt Univ. of Technol., Germany
Volume :
4
Issue :
4
fYear :
1997
fDate :
8/1/1997 12:00:00 AM
Firstpage :
365
Lastpage :
369
Abstract :
The aim of this work is to demonstrate the use of a synthetic test circuit with LC resonant circuits for fundamental experimental work on CB (vacuum circuit breakers). Studies have been performed on a 36 kV-model CB at test currents of 5 and 10 kA r.m.s. aimed at separating the influence of different parameters of the transient recovery voltage such as average rate of rise and peak value on the breaking capability. Furthermore, the effect of the arcing time on the measured arc quenching limit is presented
Keywords :
actuators; circuit resonance; circuit-breaking arcs; high-voltage techniques; power system transients; resonance; test equipment; vacuum arcs; vacuum circuit breakers; 36 to 200 kV; 5 to 25 kA; LC resonant circuits; arcing time; breaking capability; synthetic test circuit; transient recovery voltage; vacuum circuit breaker arc quenching; Circuit breakers; Circuit testing; Power system transients; RLC circuits; Resonance; Switches; Switching circuits; Vacuum arcs; Vacuum technology; Voltage;
fLanguage :
English
Journal_Title :
Dielectrics and Electrical Insulation, IEEE Transactions on
Publisher :
ieee
ISSN :
1070-9878
Type :
jour
DOI :
10.1109/94.625349
Filename :
625349
Link To Document :
بازگشت