    Increased transmission capacity by forced symmetrization

  • Author

    Glavitsch, Hans ; Rahmani, Mohanied

  • Author_Institution
    Swiss Fed. Inst. of Technol., Zurich, Switzerland
  • Volume
    13
  • Issue
    1
  • fYear
    1998
  • fDate
    2/1/1998 12:00:00 AM
  • Firstpage
    79
  • Lastpage
    85
  • Abstract
    Present planning procedures are based on single outages of three-phase circuits which do not take the actual fault pattern into account. The majority of faults are single-phase faults which is motivating the present approach to exploit the remaining conductors for power transmission. A shunt device (FACTS) is conceived which is able to generate a loading pattern at breaker locations with one or two phases open such that the network side always sees a symmetrical loading. The theoretical background is given and numerical examples illustrate the efficiency of the concept. The circuit affected by a fault may be modelled by a positive sequence impedance which can be inserted in ordinary power flow programs for security calculations
  • Keywords
    electrical faults; flexible AC transmission systems; power system planning; power system security; power transmission; EHV three-phase circuits; FACTS; breaker locations; fault pattern; forced symmetrization; loading pattern generation; planning procedures; positive sequence impedance; power flow programs; security calculations; shunt device; single-phase faults; symmetrical loading; transmission capacity improvement; Circuit faults; Conductors; Impedance; Load flow; Power system analysis computing; Power system economics; Power system planning; Power system security; Technology planning; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8950
  • Type

    jour

  • DOI
    10.1109/59.651617
  • Filename
    651617