  • Title

    Reignition surges at reactor current interruption in cable-system GIS

  • Author

    Zaima, E. ; Okabe, S. ; Nishiwaki, S. ; Ishikawa, M. ; Nakamoto, T. ; Murayama, Y. ; Kawaguchi, Y.

  • Author_Institution
    Tokyo Electr. Power Co., Japan
  • Volume
    5
  • Issue
    2
  • fYear
    1990
  • fDate
    4/1/1990 12:00:00 AM
  • Firstpage
    947
  • Lastpage
    954
  • Abstract
    A 150 MVA reactor current interruption test using a GIS (gas-insulated switchgear) on an actual 275 kV cable system and a laboratory high-frequency current interruption test using a 300 kV SF 6 gas circuit breaker were conducted. The results of these tests and their analyses, made simultaneously, permitted (1) the calculation of reignition surges and the detection of high-frequency arc extinctions caused when the reactor current was interrupted by a GIS on a cable system and (2) an evaluation of voltage escalation caused at high-frequency arc extinctions
  • Keywords
    circuit breakers; gaseous insulation; power cables; reactors (electric); sulphur compounds; surges; switchgear; 150 MVA; 245 kV; 300 kV; HF arc extinctions; SF6 gas circuit breaker; cable-system GIS; gas-insulated switchgear; power cables; reactor current; reactor current interruption test; reignition surges; voltage escalation; Circuit breakers; Circuit testing; Gas insulation; Geographic Information Systems; Inductors; Laboratories; Surges; Switchgear; System testing; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.53106
  • Filename