• DocumentCode
    1257177
  • Title

    Evaluation of the effect of pressurized bushings on seismic qualification of SF6 circuit breakers

  • Author

    Okuno, Michiharu ; Setoyama, Tatsuo ; Murase, Seiichi ; Hellested, Rolf

  • Author_Institution
    Mitsubishi Electr. Corp., Amagasaki, Japan
  • Volume
    5
  • Issue
    2
  • fYear
    1990
  • fDate
    4/1/1990 12:00:00 AM
  • Firstpage
    955
  • Lastpage
    960
  • Abstract
    It is noted that the verification of the seismic performance of power system equipment should be performed simulating the conditions experienced by the equipment when in service. Stresses on the porcelain of high-voltage switchgear under seismic vibration are statically biased by internal pressure; however, restrictions from the seismic test facility pose some difficulties in implementing practical procedures of testing with pressure. The authors discuss the effect of pressure on the strain and propose an equivalent test method to simulate a pressurized condition without actually filling the SF6 gas to the operating pressure. The equivalent nonpressurized test simulating the pressurized condition is possible by increasing the input motion amplitude by a small amount. The increase of the input motion amplitude is determined by the required increase in the total strain to simulate the static strain caused by the gas pressure
  • Keywords
    bushings; circuit breakers; gaseous insulation; sulphur compounds; HV switchgear; SF6 circuit breakers; equivalent nonpressurized test; equivalent test method; internal pressure; porcelain; power system equipment; pressurized bushings; seismic qualification; stresses; Circuit breakers; Circuit testing; Earthquakes; Frequency; Insulators; Porcelain; Qualifications; Sulfur hexafluoride; Switchgear; Vibrations;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.53107
  • Filename
    53107