• DocumentCode
    1258825
  • Title

    220-Kv. transmission line for the Conowingo development

  • Author

    Chase, P.H.

  • Author_Institution
    Transmission & Distribution Division, The Philadelphia Electric Company
  • Volume
    47
  • Issue
    10
  • fYear
    1928
  • Firstpage
    752
  • Lastpage
    756
  • Abstract
    Current from the Conowingo plant is carried fifty-eight miles to the Plymouth Meeting Substation of The Philadelphia Electric Company over two 220-kv. single-circuit steel-tower transmission lines. These lines are carried on a right-of-way which provides space for a third future line. The conductors are 795,000-cir. mil steel-reinforced aluminum. Each circuit is shielded by two 183,600-cir. mil aluminum steel-reinforced ground wires. The insulator strings consist of 14 high-strength units in suspension position and 16 units in strain position. Conductors and ground wires are carried in a new type of slip clamp in order to decrease the unbalanced longitudinal stresses on the towers in the event of wire breakage. In general, foundations are of the earth grillage type. The tower design includes a number of novel features, among them the use of combination extensions to flexibly meet the varying topographical conditions, and the narrow waist immediately below the basket.
  • fLanguage
    English
  • Journal_Title
    A.I.E.E., Journal of the
  • Publisher
    ieee
  • ISSN
    0095-9804
  • Type

    jour

  • DOI
    10.1109/JAIEE.1928.6534441
  • Filename
    6534441