DocumentCode
1259161
Title
Frequency dependence of breakdown performance of XLPE with different artificial defects
Author
Li, Weiwei ; Li, Jianying ; Yin, Guilai ; Li, Shengtao ; Zhao, Jiankang ; Ouyang, Benhong ; Ohki, Yoshimichi
Author_Institution
State Key Lab. of Electr. Insulation & Power Equip., Xi´´an Jiaotong Univ., Xi´´an, China
Volume
19
Issue
4
fYear
2012
fDate
8/1/2012 12:00:00 AM
Firstpage
1351
Lastpage
1359
Abstract
In this paper, the effect of the applied field frequency on the breakdown performances of cross-linked polyethylene (XLPE) insulation was investigated. Three kinds of artificial defects, namely an inserted needle, a needle void and a knife void, were introduced into a 10 kV commercial XLPE cable, to simulate real defects that may be introduced during on-site service. Breakdown tests were conducted in transformer oil at room temperature using a frequency-tuned resonant test system in a frequency range from 20 to 300 Hz. It was found that the breakdown voltage of specimens with the inserted needle was sensitive to the applied field frequency, and the breakdown voltage showed a maximum value at about 240 Hz. However, for other two kinds of specimens with the needle void and knife void, the breakdown behavior shows a weak relation with the applied field frequency. The breakdown voltages of the specimens with the needle and void are 25 kV and 20 kV respectively. It was further found that side channels appeared on the flank of the main channel of the breakdown path in the specimen with the inserted needle, and the frequency dependence of fractal dimension D of the side channel in the breakdown path are similar to that of electrical trees before breakdown, which may consequently lead to the maximum value in the experimental results.
Keywords
polyethylene insulation; transformer oil; trees (electrical); XLPE; applied field frequency; artificial defects; breakdown performance; breakdown voltage; cross-linked polyethylene insulation; electrical trees; frequency 20 Hz to 300 Hz; frequency dependence; frequency-tuned resonant test system; knife void; needle void; temperature 293 K to 298 K; transformer oil; voltage 20 kV; voltage 25 kV; Cable insulation; Electric breakdown; Fractals; Needles; Resonant frequency; Space charge; Cross-linked polyethylene; breakdown performance; fractal dimension; frequency-tuned resonant systems;
fLanguage
English
Journal_Title
Dielectrics and Electrical Insulation, IEEE Transactions on
Publisher
ieee
ISSN
1070-9878
Type
jour
DOI
10.1109/TDEI.2012.6260011
Filename
6260011
Link To Document