Title :
Touch voltages on underground distribution systems during fault conditions
Author :
Rajotte, Yves ; Bergeron, Roger ; Chalifoux, Alain ; Gervais, Yvon
Author_Institution :
IREQ, Varennes, Que., Canada
fDate :
4/1/1990 12:00:00 AM
Abstract :
Underground distribution lines are usually installed in duct banks with manholes placed at regular intervals for easy installation of the line hardware and ready access for maintenance purposes. During work in these manholes, tough voltages may occur on the line under repair as a result of a fault on another line. Tests were performed on a 25 kV grounded-wye system to measure the level of such voltage and to validate a computer model. The maximum touch voltage measured was 220 V. Over 6000 system configurations were examined in a computer study which showed that the touch voltage appearing at the work site can reach as much as 1500 V in some cases, although operating experience shows that the probability of such high voltages is very slight
Keywords :
electrical faults; power engineering computing; underground distribution systems; 1500 V; 220 V; 25 kV; computer model; duct banks; fault conditions; grounded-wye system; tough voltages; underground distribution systems; Cables; Conductors; Ducts; Hardware; Performance evaluation; Protection; Research and development; System testing; Transmission lines; Voltage measurement;
Journal_Title :
Power Delivery, IEEE Transactions on