DocumentCode :
1264985
Title :
Effects of underexcitation limiters on operation of remote generating station
Author :
Choi, S.S. ; Larkin, R. ; Bastick, M.T. ; Ferres, A.W.
Author_Institution :
State Energy Comm. of Western Australia, Perth, WA, Australia
Volume :
138
Issue :
6
fYear :
1991
fDate :
11/1/1991 12:00:00 AM
Firstpage :
560
Lastpage :
566
Abstract :
Results of an investigation into reported incidents of network voltage instability within a 132 kV transmission network in Western Australia are presented. The cause of the problem was found to be inappropriate settings of the under excitation limiters on two recently installed gas turbines. It is shown, through simulation studies, how the limiter settings can be modified to overcome the stability problem. Results of tests validate the effectiveness of the proposed modifications
Keywords :
stability; transmission networks; 132 kV; Western Australia; gas turbines; network voltage instability; remote generating station; transmission network; underexcitation limiters;