Conservation Voltage Reduction (CVR) at Northeast Utilities
Author
Lauria, D. M.
Author_Institution
Northeast Utilities, Hartford, CT
Issue
10
fYear
1987
Firstpage
58
Lastpage
59
Abstract
This paper presents the results of field tests conducted on the Northeast Utilities (NU) distribution system in Connecticut to measure changes in energy consumption resulting from voltage reduction. The economies of achieving a permanent voltage reduction by compressing existing state voltage limits to a narrower band is also examined. Although the field tests indicate that there are energy savings associated with voltage reduction, it is uneconomical to achieve voltage reduction on the NU system by compressing existing voltage limits. The use of existing line drop compensation controls is identified as a practical method of achieving voltage reduction without changing existing voltage limits.