Title :
Application of an On-Line Air-Gap Monitor for Hydroelectric Generator Protection and Problem Diagnosis
Author :
Talas, P. ; Toom, P.O. ; Franklin, D.E. ; Palylyk, R.A.
Author_Institution :
B.C. Hydro and Power Authority, Vancouver, BC, Canada
Abstract :
This paper presents the application of a new hydroelectric generator air-gap measurement system. It is a continuous on-line system using optical triangulation, fiber-optics, a microprocessor-based monitor, specially developed instrumentation and power supplies. This system is noninvasive, insensitive to EMI, and has 0.2 percent accuracy over a range of 2 to 40 mm. The paper presents air-gap data obtained from B.C. Hydro´s Mica Creek Unit G2 (457 MVA) during March 1986. Readings were taken from stator-to-rotor and from rotor-to-stator to determine the unit´s characteristics prior to rotor rim shrink modifications. These data assisted in determining the individual contributions of the rotor and the stator to the generator´s behavior and provides a comparison for post-modification testing.
Keywords :
Air gaps; Electromagnetic interference; Hydroelectric power generation; Instruments; Monitoring; Optical fibers; Power supplies; Power system protection; Rotors; Stators;
Journal_Title :
Power Engineering Review, IEEE
DOI :
10.1109/MPER.1987.5526824