DocumentCode
1269168
Title
Recovery of breakdown strength of a vacuum interrupter after extinction of high currents
Author
Schade, E. ; Dullni, E.
Author_Institution
ABB Corporate Res. Ltd., Baden-Daettwil, Switzerland
Volume
9
Issue
2
fYear
2002
fDate
4/1/2002 12:00:00 AM
Firstpage
207
Lastpage
215
Abstract
Relevant phenomena during the period of the recovery of the dielectric strength of vacuum interrupter (VI) are reviewed. Metal vapor, residual charge and the effects of molten contact surfaces reduce the breakdown strength after the interruption of high currents. Metal droplets seem to play only a secondary role during the recovery phase. Instability of liquid protrusions is suspected to initiate breakdown if the electric field strength exceeds 10 kV/mm at the molten contact surfaces (undisturbed field). Key parameters are surface temperature and vapor density. Breakdown during recovery of the dielectric strength depends not only on the value of the voltage applied but also on the duration of the high voltage stress. A spontaneous triggering event in the presence of metal vapor appears to initiate breakdown at conditions below the Paschen breakdown limit. This type of breakdown events limits the interruption performance of VI´s.
Keywords
electric breakdown; electric strength; vacuum interrupters; Paschen breakdown; breakdown strength; dielectric strength; high current extinction; liquid protrusion instability; metal droplet; metal vapor; molten contact surface; recovery phase; residual charge; surface temperature; vacuum interrupter; vapor density; Dielectric breakdown; Electric breakdown; Interrupters; Magnetic fields; Plasma temperature; Short circuit currents; Switches; Testing; Vacuum breakdown; Voltage;
fLanguage
English
Journal_Title
Dielectrics and Electrical Insulation, IEEE Transactions on
Publisher
ieee
ISSN
1070-9878
Type
jour
DOI
10.1109/94.993737
Filename
993737
Link To Document