Single-pole short-circuit interruption of molded-case circuit breakers
Author :
Gregory, George D.
Author_Institution :
Square D Co., Cedar Rapids, IA, USA
Volume :
35
Issue :
6
fYear :
1999
Firstpage :
1265
Lastpage :
1270
Abstract :
Short-circuit tests of individual poles of molded-case circuit breakers are required under North American industry standards. Test current is intentionally at a limited fault availability level rather than at the interrupting rating of the circuit breaker. This paper clarifies the single-pole test requirements. It then examines the potential fault conditions under a variety of systems and provides application guidelines considering the potential fault conditions
Keywords :
circuit breakers; electrical faults; interrupters; switchgear testing; North American industry standards; application guidelines; fault availability level; interrupting rating; moulded-case circuit breakers; potential fault conditions; single-pole short-circuit interruption tests; single-pole test requirements; Circuit breakers; Circuit faults; Circuit testing; Conductors; Grounding; Guidelines; Leg; National electric code; System testing; Voltage;