• DocumentCode
    1271421
  • Title

    Effects of very fast transient overvoltages on transformer

  • Author

    Shibuya, Y. ; Fujita, S. ; Shimomura, T.

  • Author_Institution
    Mitsubishi Electr. Corp., Amagasaki, Japan
  • Volume
    146
  • Issue
    5
  • fYear
    1999
  • fDate
    9/1/1999 12:00:00 AM
  • Firstpage
    459
  • Lastpage
    464
  • Abstract
    An analytical solution is found using the Laplace transform to describe the very fast transient overvoltage (VFTO) in the gas insulated switchgear (GIS) connected directly to a transformer. The oscillation frequencies, and other properties, are explicitly given in terms of system parameters. The magnitude of VFTO at the transformer is suppressed due to the transformer capacitance, Magnitudes of the initial abrupt voltage change and oscillatory voltage are assessed. The abrupt voltage is larger, but not enough to induce a harmful voltage in the transformer. The oscillatory components may damage the winding insulation at the occurrence of resonance
  • Keywords
    Laplace transforms; gas insulated switchgear; overvoltage; power system transients; power transformers; transformer windings; Laplace transform; gas insulated switchgear; initial abrupt voltage change; oscillation frequencies; oscillatory voltage; power transformer; transformer capacitance; very fast transient overvoltages; winding insulation damage;
  • fLanguage
    English
  • Journal_Title
    Generation, Transmission and Distribution, IEE Proceedings-
  • Publisher
    iet
  • ISSN
    1350-2360
  • Type

    jour

  • DOI
    10.1049/ip-gtd:19990425
  • Filename
    806190