DocumentCode
1271421
Title
Effects of very fast transient overvoltages on transformer
Author
Shibuya, Y. ; Fujita, S. ; Shimomura, T.
Author_Institution
Mitsubishi Electr. Corp., Amagasaki, Japan
Volume
146
Issue
5
fYear
1999
fDate
9/1/1999 12:00:00 AM
Firstpage
459
Lastpage
464
Abstract
An analytical solution is found using the Laplace transform to describe the very fast transient overvoltage (VFTO) in the gas insulated switchgear (GIS) connected directly to a transformer. The oscillation frequencies, and other properties, are explicitly given in terms of system parameters. The magnitude of VFTO at the transformer is suppressed due to the transformer capacitance, Magnitudes of the initial abrupt voltage change and oscillatory voltage are assessed. The abrupt voltage is larger, but not enough to induce a harmful voltage in the transformer. The oscillatory components may damage the winding insulation at the occurrence of resonance
Keywords
Laplace transforms; gas insulated switchgear; overvoltage; power system transients; power transformers; transformer windings; Laplace transform; gas insulated switchgear; initial abrupt voltage change; oscillation frequencies; oscillatory voltage; power transformer; transformer capacitance; very fast transient overvoltages; winding insulation damage;
fLanguage
English
Journal_Title
Generation, Transmission and Distribution, IEE Proceedings-
Publisher
iet
ISSN
1350-2360
Type
jour
DOI
10.1049/ip-gtd:19990425