DocumentCode :
1271784
Title :
Field Measurement of Ground Fault Current Distribution and Substation Ground Impedance at LG-2, Qu??bec
Author :
Fortin, J. ; Sarmiento, H.G. ; Mukhedkar, D.
Author_Institution :
Essais de r??seau et Analyse, Hydro-Qu??bec, Montr??al, Canada
Issue :
7
fYear :
1986
fDate :
7/1/1986 12:00:00 AM
Firstpage :
29
Lastpage :
29
Abstract :
Field measurements of ground fault current distribution and substation ground impedance of the LG-2 complex in Quebec, are presented. A high current measuring technique is described in Appendix A. Appendix B illustrates the way current distribution and efficiency were determined. The effectiveness of each grounding element is calculated, showing that the grounding conductors and not the ground grid drain most of the fault current.
Keywords :
Conductors; Current distribution; Current measurement; Electrodes; Fault currents; Grounding; Impedance measurement; Substations; Testing; Wires;