Abstract
Microprocessor based relays have advanced algorithms in them to provide enhanced security against transients and other conditions that cannot actually exist on a real power system. This means that test methods should mimic real power system conditions, otherwise the relay may not operate or operate in an unpredictable manner for unrealistic conditions that are presented by a test set. This has given rise to the common phrase “test the tester”. This paper will show common mistakes that are made when testing Microprocessor based relays with unrealistic power system conditions. The paper also explains why these conditions are unrealistic, and explains how typical relay algorithms respond to these conditions. Unrealistic tests to be explored will include: a step change in frequency for under-frequency testing, absence of pre-fault conditions when testing distance elements, change in voltage phase when testing distance elements, improperly set zero sequence compensation factors in test set software, and improper phase direction on bus protection.
Keywords
relay protection; testing; bus protection; microprocessor based relays; pre-fault conditions; test set software; under-frequency testing; unrealistic power system conditions; zero sequence compensation factors; Erbium; Testing; Time-frequency analysis;
fLanguage
English
Publisher
ieee
Conference_Titel
Protective Relay Engineers, 2014 67th Annual Conference for
Conference_Location
College Station, TX
Print_ISBN
978-1-4799-4740-9
Type
conf
DOI
10.1109/CPRE.2014.6799033
Filename
6799033
Link To Document