DocumentCode
127571
Title
Low second-harmonic content in transformer inrush currents - Analysis and practical solutions for protection security
Author
Hodder, Steven ; Kasztenny, Bogdan ; Fischer, Normann ; Yu Xia
Author_Institution
Hydro One Networks, Inc., USA
fYear
2014
fDate
March 31 2014-April 3 2014
Firstpage
705
Lastpage
722
Abstract
This paper addresses the security of transformer differential protection with low levels of second harmonic during magnetizing inrush conditions. The paper explains the phenomenon of ultrasaturation causing the second harmonic to drop below the traditional 15 to 20 percent setting levels and points to possible causes of and conditions for ultrasaturation. A number of field cases are presented and discussed in addition to the engineering analysis of the problem. The paper outlines several simple solutions to address the security problem while minimizing the adverse impact on dependability. Further, the paper presents a new method for inrush detection that considerably improves security without diminishing dependability. Finally, a method to accelerate operation of transformer differential protection is presented.
Keywords
power transformer protection; adverse impact minimization; engineering analysis; inrush detection; magnetizing inrush conditions; protection security; second-harmonic content; transformer differential protection security; transformer inrush currents; ultrasaturation phenomenon; Circuit faults; Harmonic analysis; Magnetic flux; Permeability; Saturation magnetization; Security; Transformer cores;
fLanguage
English
Publisher
ieee
Conference_Titel
Protective Relay Engineers, 2014 67th Annual Conference for
Conference_Location
College Station, TX
Print_ISBN
978-1-4799-4740-9
Type
conf
DOI
10.1109/CPRE.2014.6799037
Filename
6799037
Link To Document