DocumentCode :
1276600
Title :
Generator coherency and area detection in large power systems
Author :
Vahidnia, Arash ; Ledwich, Gerard ; Palmer, Everett ; Ghosh, A.
Author_Institution :
Sch. of Electr. Eng. & Comput. Sci., Queensland Univ. of Technol., Brisbane, QLD, Australia
Volume :
6
Issue :
9
fYear :
2012
fDate :
9/1/2012 12:00:00 AM
Firstpage :
874
Lastpage :
883
Abstract :
This study provides a new general approach for defining coherent generators in power systems based on the coherency in low-frequency inter-area modes. The disturbance is considered to be distributed in the network by applying random load changes which is the random walk representation of real loads instead of a single fault and coherent generators are obtained by spectrum analysis of the generators velocity variations. In order to find the coherent areas and their borders in the inter-connected networks, non-generating buses are assigned to each group of coherent generator using similar coherency detection techniques. The method is evaluated on two test systems and coherent generators and areas are obtained for different operating points to provide a more accurate grouping approach which is valid across a range of realistic operating points of the system.
Keywords :
power system faults; power system interconnection; area detection; coherency detection techniques; general approach; generator coherency; generators velocity variations; grouping approach; interconnected networks; large power systems; low-frequency inter-area modes; nongenerating buses; operating points; random load changes; random walk representation; spectrum analysis;
fLanguage :
English
Journal_Title :
Generation, Transmission & Distribution, IET
Publisher :
iet
ISSN :
1751-8687
Type :
jour
DOI :
10.1049/iet-gtd.2012.0091
Filename :
6291224
Link To Document :
بازگشت