• DocumentCode
    1276648
  • Title

    Optimum message transfer rate for distribution feeder protection operating over switched telephone networks

  • Author

    Li, H.Y. ; Crossley, P.A.

  • Author_Institution
    Dept. of Electr. Eng. & Electron., Univ. of Manchester Inst. of Sci. & Technol., UK
  • Volume
    17
  • Issue
    2
  • fYear
    2002
  • fDate
    4/1/2002 12:00:00 AM
  • Firstpage
    353
  • Lastpage
    358
  • Abstract
    Distribution feeder protection relays require reliable and low cost communication channels. The reliability in sending protection messages over a private or a public switched telephone network (STN) and the associated communication time delay are considered in this paper. The reasoning used to determine the optimum message transfer rate for a numerical current differential relay used for distribution feeder protection is described. A communication channel testing facility was developed and used to measure the time delay necessary to reliably send a protection message over an STN channel operating at different modem data rates. This paper presents and discusses the results obtained and shows how they can be validated using an analytical expression for data transfer reliability. For the defined current differential message frame, test results show that the selected data speed maximizes channel reliability and minimizes channel delay
  • Keywords
    data communication; power distribution protection; relay protection; telephone networks; channel delay minimisation; channel reliability maximisation; communication channel testing facility; communication time delay; current differential message frame; data transfer reliability; distribution feeder protection; distribution feeder protection relays; numerical current differential relay; optimum message transfer rate; private switched telephone networks; public switched telephone networks; time delay measurement; Communication channels; Communication switching; Costs; Delay effects; Protection; Protective relaying; Telecommunication network reliability; Telephony; Testing; Time measurement;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.997898
  • Filename
    997898