DocumentCode
1276769
Title
Fault location using voltage measurements
Author
Galijasevic, Zijad ; Abur, Ali
Author_Institution
Dept. of Electr. Eng., Texas A&M Univ., College Station, TX, USA
Volume
17
Issue
2
fYear
2002
fDate
4/1/2002 12:00:00 AM
Firstpage
441
Lastpage
445
Abstract
This paper presents a novel method for locating short-circuit faults in electric power systems. The origins of the method are in the concept of vulnerability contours which is used in assessing the likelihood of voltage sags effecting a given network area. The method is applied in an the off-line step and an on-line step. On-line step consists of measuring voltage sags at selected system buses. Off-line step consists of estimating the most likely fault location by matching measured voltage sags with the ones calculated through the fault simulations. In the process, the fault resistance is estimated as well. To cope with the inherent uncertainty in the problem, the fuzzy logic reasoning is applied. The performance of the method is demonstrated using some typical examples. Since the actual measurements of voltage sags were unavailable, fault simulations were conducted to emulate real measuring process
Keywords
fault location; fuzzy logic; inference mechanisms; power supply quality; power system faults; voltage measurement; electric power systems; fault location; fault resistance estimation; fault simulation; fuzzy logic reasoning; off-line step; on-line step; short-circuit faults; system buses; voltage measurements; voltage sags measurement; vulnerability contours; Electrical resistance measurement; Fault location; Fuzzy logic; Instruments; Monitoring; Power quality; Power system faults; Substations; System buses; Voltage measurement;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/61.997915
Filename
997915
Link To Document