• DocumentCode
    1276769
  • Title

    Fault location using voltage measurements

  • Author

    Galijasevic, Zijad ; Abur, Ali

  • Author_Institution
    Dept. of Electr. Eng., Texas A&M Univ., College Station, TX, USA
  • Volume
    17
  • Issue
    2
  • fYear
    2002
  • fDate
    4/1/2002 12:00:00 AM
  • Firstpage
    441
  • Lastpage
    445
  • Abstract
    This paper presents a novel method for locating short-circuit faults in electric power systems. The origins of the method are in the concept of vulnerability contours which is used in assessing the likelihood of voltage sags effecting a given network area. The method is applied in an the off-line step and an on-line step. On-line step consists of measuring voltage sags at selected system buses. Off-line step consists of estimating the most likely fault location by matching measured voltage sags with the ones calculated through the fault simulations. In the process, the fault resistance is estimated as well. To cope with the inherent uncertainty in the problem, the fuzzy logic reasoning is applied. The performance of the method is demonstrated using some typical examples. Since the actual measurements of voltage sags were unavailable, fault simulations were conducted to emulate real measuring process
  • Keywords
    fault location; fuzzy logic; inference mechanisms; power supply quality; power system faults; voltage measurement; electric power systems; fault location; fault resistance estimation; fault simulation; fuzzy logic reasoning; off-line step; on-line step; short-circuit faults; system buses; voltage measurements; voltage sags measurement; vulnerability contours; Electrical resistance measurement; Fault location; Fuzzy logic; Instruments; Monitoring; Power quality; Power system faults; Substations; System buses; Voltage measurement;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.997915
  • Filename
    997915