  • Abstract
    With the advent of the high synchronization accuracy of modern phasor measurement units (PMUs), a new approach for accurately locating faults on three-terminal lines is proposed. Using the data measured from two terminals of three-terminal lines, the proposed technique can provide an extremely accurate fault location. An EMTP/ATP simulator is used to demonstrate the performance of the proposed fault locator. The simulation results show that the accuracy of fault location is very high under various fault resistance, fault locations, prefault loading conditions, source impedance and fault types
  • Keywords
    EMTP; electric current measurement; fault location; power system measurement; power transmission faults; power transmission lines; synchronisation; voltage measurement; EMTP/ATP simulator; fault locator; fault resistance; high synchronization accuracy; phasor measurement units; prefault loading conditions; source impedance; three-terminal lines; three-terminal transmission lines; two-terminal synchronized current phasors; two-terminal synchronized voltage phasors; Costs; Electrical resistance measurement; Error correction; Fault location; Phasor measurement units; Power system protection; Power transmission lines; Transmission line measurements; Transmission lines; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.997917
  • Filename
    997917