Abstract
The characteristic of the single-phase earth fault in the Peterse coil grounded distribution network is discussed in this paper. It is disclosed that only the derivative of the zero-sequence current of the faulty feeder changes with the controllable inductance of the Petersen coil, while the derivative of the zero-sequence current of the sound feeder is kept invariable. Therefore, a novel faulty feeder selection criterion is proposed. A variety of simulation tests is carried out. The exactness and sensitivity of the proposed scheme are verified by simulation test results.
Keywords
coils; earthing; fault location; power distribution faults; power distribution protection; adaptive Petersen coil control; coil grounded distribution network; fault self-extinguishing; faulty feeder detection; sound feeder; zero-sequence current; Adaptive Petersen coil; maximum current derivative; residual current; resonant grounding; self-extinguish;