DocumentCode
128110
Title
A novel technique for impedance relay to locate fault in long transmission line
Author
Kumar, Ravindra ; Kumar, Sudhakar
Author_Institution
Power Grid Corp. of India Ltd., India
fYear
2014
fDate
6-8 March 2014
Firstpage
1
Lastpage
6
Abstract
In this paper distributed parameters based a novel algorithm for finding location of fault in long transmission line is presented. Presently relay manufacturers use impedance based algorithm considering the lumped parameters even for long transmission line. Lumped parameters based gives accurate results for short transmission line, but fails to produce good accuracy in long transmission lines. This paper draws the attention of manufacturer to use distributed parameters based algorithm in long transmission line to get correct location of fault. A mathematical model is developed for proposed technique and a simulation model is developed for proposed fault locator in MATLAB for short and long transmission line. Simulation results are validated from actual field results and the results obtained from two different make relays.
Keywords
fault location; power transmission faults; power transmission lines; relay protection; MATLAB; distributed parameters based algorithm; fault location; impedance relay; long transmission line; lumped parameters; mathematical model; short transmission line; simulation model; Fault location; Impedance; Mathematical model; Numerical models; Power transmission lines; Relays; Transmission line measurements; Digital Protection Relay; Fault locator; Impedance relay; Transmission system protection; numerical relay;
fLanguage
English
Publisher
ieee
Conference_Titel
Engineering and Computational Sciences (RAECS), 2014 Recent Advances in
Conference_Location
Chandigarh
Print_ISBN
978-1-4799-2290-1
Type
conf
DOI
10.1109/RAECS.2014.6799526
Filename
6799526
Link To Document