Title :
Improved voltage and reactive power distribution factors for outage studies
Author :
Singh, S.N. ; Srivastava, S.C.
Author_Institution :
Dept. of Electr. Eng., Indian Inst. of Technol., Kanpur, India
fDate :
8/1/1997 12:00:00 AM
Abstract :
This paper presents the development of a simple and fast method to calculate a new set of distribution factors using the sensitivity property of Newton-Raphson load flow Jacobian at a base operating point. These factors have been used to calculate the post-outage voltages and reactive power output of the sources following outage of a transmission branch or a generator. The accuracy of post-outage results using these distribution factors has been established with respect to full AC load flow results on IEEE 14-bus, IEEE 57-bus and a practical 75-bus Indian power systems
Keywords :
Jacobian matrices; Newton-Raphson method; electrical faults; load flow; power system analysis computing; power system security; power system stability; reactive power; voltage distribution; AC load flow; Newton-Raphson load flow Jacobian; base operating point; computer simulation; distribution factors; post-outage voltages; power system outages; reactive power output; sensitivity property; Jacobian matrices; Load flow; Load flow analysis; Power engineering and energy; Power generation; Power system security; Predictive models; Reactive power; Senior members; Voltage;
Journal_Title :
Power Systems, IEEE Transactions on