• DocumentCode
    1290746
  • Title

    Loads on delta-connected transformers with mid-taps

  • Author

    Larson, Noble G.

  • Author_Institution
    Commonwealth Edison Co. Chicago, Ill.
  • Volume
    54
  • Issue
    9
  • fYear
    1935
  • Firstpage
    931
  • Lastpage
    934
  • Abstract
    Mid-taps on the secondaries of a 3-phase delta-connected transformer bank enable loads to be supplied simultaneously at full voltage and half voltage. Although the nonuniform loading of the different windings makes an exact determination of the maximum permissible loads difficult, equations and curves have been developed to facilitate these calculations. A rating factor is included which permits the rating of the transformer bank to be expressed in terms of the maximum current in any portion of the windings. Equations for voltage regulation with balanced loads and similar transformer units have been developed.
  • fLanguage
    English
  • Journal_Title
    Electrical Engineering
  • Publisher
    ieee
  • ISSN
    0095-9197
  • Type

    jour

  • DOI
    10.1109/EE.1935.6540165
  • Filename
    6540165