DocumentCode :
1291065
Title :
Modeling of copper sulphide migration in paper oil insulation of transformers
Author :
Rudranna, N. ; Rajan, J. Sundara
Author_Institution :
Electr. Eng. Dept., R.V. Coll. of Eng., Bangalore, India
Volume :
19
Issue :
5
fYear :
2012
fDate :
10/1/2012 12:00:00 AM
Firstpage :
1642
Lastpage :
1649
Abstract :
Corrosion of copper due to sulphur in oil has affected the performance of transformers. The fundamental processes governing corrosion of copper due to sulphur in oil are still not well understood. In this paper, the dielectric performance of paper oil insulation under conditions of copper sulphide is discussed based on changes in capacitance, Insulation resistance and Partial discharges. Electric field analysis using FEM and PD results are employed to develop an empirical model to predict PD inception of paper oil insulation when copper sulphide is present. A simple model is also proposed to explain progressive copper sulphide migration in paper insulation. The non-linear V-I characteristics of copper sulphide is discussed to explain the breakdown of paper-oil insulation.
Keywords :
finite element analysis; partial discharges; power transformer insulation; transformer oil; FEM; PD inception; dielectric performance; electric field analysis; empirical model; insulation resistance; migration; nonlinear V-I characteristics; paper oil insulation; partial discharges; power transformers; Aging; Copper; Finite element methods; Oil insulation; Partial discharges; Stress; Copper corrosion; copper sulphide; metalpassivator; partial discharge (PD); power transformer;
fLanguage :
English
Journal_Title :
Dielectrics and Electrical Insulation, IEEE Transactions on
Publisher :
ieee
ISSN :
1070-9878
Type :
jour
DOI :
10.1109/TDEI.2012.6311511
Filename :
6311511
Link To Document :
بازگشت