  • Title

    Transferring of VFTO From an EHV to MV System as Observed in Taiwan´s No. 3 Nuclear Power Plant

  • Author

    Lee, Chang-Hsing ; Hsu, Shih-Che ; Hsi, Pao-Hsiang ; Chen, Shi-Lin

  • Author_Institution
    Nat. Tsing Hua Univ., Hsinchu, Taiwan
  • Volume
    26
  • Issue
    2
  • fYear
    2011
  • fDate
    4/1/2011 12:00:00 AM
  • Firstpage
    1008
  • Lastpage
    1016
  • Abstract
    The severe insulation breakdown on one medium-voltage (MV) switchgear led to a complete blackout of Taipower´s 3rd nuclear power plant on March 18th, 2001. This has been one of the most serious incidents during the past 30 years of Taipower´s nuclear generation and while the cause of the event was a combination of design, maintenance, and equipment aging issue, it is apparent that repeated switching operation on the extra-high-voltage (EHV) side eventually caused this severe insulation breakdown on MV switchgear. Very-fast transient overvoltage (VFTO) is the phenomenon of transient overvoltage generated during switching operation characterized by a very short rise time of 4 to 100 ns. Prior research on this topic focused on VFTO´s impact on the EHV side of the transformer and this paper presents the field measurement result together with long-duration multiple-restrike simulation for the VFTO transferred from the EHV side to the MV system through the power transformers. It is shown that this VFTO can be as high as 7 times the rated line-to-ground peak voltage and the maximum VFTO often occusr neither at the first nor at the last strike due to the superposition of restriking voltage on top of oscillation voltage created by prior strikes.
  • Keywords
    nuclear power stations; overvoltage protection; power system measurement; power system transients; VFTO; insulation breakdown; medium-voltage switchgear; nuclear power plant; power transformers; very-fast transient overvoltage; Electromagnetic Transients Program (EMTP); gas-insulated substation; medium-voltage (MV) system; multiple-restrike; very-fast transient overvoltage (VFTO);
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/TPWRD.2010.2054838