DocumentCode :
1296877
Title :
Electrical strength of towers in 500-kv design
Author :
Johnson, Wallace R. ; Lambert, E.G. ; Tice, J.B. ; Turner, F.J.
Author_Institution :
Pacific Gas and Electric Co., San Francisco, Calif.
Volume :
82
Issue :
6
fYear :
1963
fDate :
6/1/1963 12:00:00 AM
Firstpage :
382
Lastpage :
387
Abstract :
Tests have been conducted on transmission towers to establish flashover levels of switching-surge, impulse, and GO-cycle voltages for use in the design of structures for a SOO-fcv line. The tests on the actual tower verified the adequacy of the design to withstand switching surges of 2.5 times the maximum operating voltage of 550 kv for a line constructed at an average elevation of 5,000 feet