• DocumentCode
    1296877
  • Title

    Electrical strength of towers in 500-kv design

  • Author

    Johnson, Wallace R. ; Lambert, E.G. ; Tice, J.B. ; Turner, F.J.

  • Author_Institution
    Pacific Gas and Electric Co., San Francisco, Calif.
  • Volume
    82
  • Issue
    6
  • fYear
    1963
  • fDate
    6/1/1963 12:00:00 AM
  • Firstpage
    382
  • Lastpage
    387
  • Abstract
    Tests have been conducted on transmission towers to establish flashover levels of switching-surge, impulse, and GO-cycle voltages for use in the design of structures for a SOO-fcv line. The tests on the actual tower verified the adequacy of the design to withstand switching surges of 2.5 times the maximum operating voltage of 550 kv for a line constructed at an average elevation of 5,000 feet