Title :
Generator loss of field study for AEP´s Rockport plant
Author :
Rana, Raju D. ; Schulz, Richard P. ; Heyeck, Michael ; Boyer, Theodore R., Jr.
Author_Institution :
American Electric Power Service Corp., New York, NY, USA
fDate :
4/1/1990 12:00:00 AM
Abstract :
The computed performance of American Electric Power´s remotely located 2600 MW Rockport plant after simulated generator loss-of-field (LOF) disturbances to one of its 1300 MW cross-compound units is described. LOF conditions are reviewed, and AEP´s experience and practice in dealing with such conditions are examined. The modeling used in the computer simulation analyses is discussed. Two simulation analyses are considered: LOF on a high pressure generator with no prior disturbance and, more briefly, LOF on a reheat turbine generator with no prior disturbance. Studies of potential false operation and plans for future LOF analyses are discussed.<>
Keywords :
digital simulation; electrical faults; power engineering computing; power stations; turbogenerators; 1300 MW; 2600 MW; USA; computer simulation; disturbances; electrical faults; false operation; generator loss-of-field; modeling; performance; power engineering computing; power stations; Analytical models; Computational modeling; Computer simulation; Performance loss; Power generation; Turbines;
Journal_Title :
Computer Applications in Power, IEEE