• DocumentCode
    1303498
  • Title

    NEC grounding requirements for parallel circuits

  • Author

    Daly, James M.

  • Author_Institution
    BICC Cables Corp., West Nyack, NY, USA
  • Volume
    4
  • Issue
    2
  • fYear
    1998
  • Firstpage
    37
  • Lastpage
    41
  • Abstract
    This article specifically addresses the requirements of Table 250-95 of the National Electrical Code(R) (NEC) for proper sizing of the equipment grounding conductors in parallel circuits. However, it must be remembered that the grounding path must also comply with Section 250-51, in particular (3), which requires that the grounding path have sufficiently low impedance to limit the voltage to ground and to facilitate the operation of the circuit protective devices. The note to Table 250-95 emphasizes the point that the equipment grounding conductors may need to be sized larger than specified in this table in order to comply with Section 250-51. The recommendations presented herein are based on a literal interpretation by the author of the NEC as written and may not necessarily agree with the Code Making Panel´s intent
  • Keywords
    conductors (electric); earth electrodes; standards; NEC grounding requirements; National Electrical Code; Section 250-51; Table 250-95; circuit protective devices; equipment grounding conductors sizing; grounding path; low impedance; parallel circuits; voltage to ground limiting; Aluminum; Cables; Circuits; Conducting materials; Conductors; Copper; Grounding; National electric code; Protection; Voltage;
  • fLanguage
    English
  • Journal_Title
    Industry Applications Magazine, IEEE
  • Publisher
    ieee
  • ISSN
    1077-2618
  • Type

    jour

  • DOI
    10.1109/2943.655659
  • Filename
    655659