DocumentCode
1304809
Title
Effect of the Formation of the Dry Zone Around Underground Power Cables on Their Ratings
Author
Gouda, Ossama E. ; El Dein, Adel Z. ; Amer, Ghada M.
Author_Institution
Dept. of Electr. Eng., Cairo Univ., Cairo, Egypt
Volume
26
Issue
2
fYear
2011
fDate
4/1/2011 12:00:00 AM
Firstpage
972
Lastpage
978
Abstract
Many factors affect the loading of the underground power cables, such as ambient temperature, depth of laying of cable, number of parallel circuits of cable, and thermal resistivity of the surrounding soil. One important factor, usually ignored, is the formation of dry zones around the underground power cables. Dry zones are usually formed around underground power cables under loading conditions due to the migration of moisture within the soil. In this paper, the effect of the formation of the dry zone on the ampacity of underground power cables is investigated. The derating factor for the formation of dry zones around underground power cables is suggested and calculated for different types of natural backfill soil. IEC 60287-1-3 is taken as a reference. Experimental work was conducted to study the phenomena of the dry zone as related to different types of soils.
Keywords
IEC standards; power cables; soil; thermal conductivity; underground cables; IEC 60287-1-3; dry zone; natural backfill soil; parallel circuits; thermal resistivity; underground power cables; Cable ampacity; de-rating factor; dry zone; temperature distribution;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/TPWRD.2010.2060369
Filename
5557780
Link To Document