DocumentCode :
1305341
Title :
Optimal exploitation of generator-transformer units
Author :
Losi, A. ; Mangoni, V. ; Russo, M.
Author_Institution :
Dipartimento di Ingegneria Ind., Cassino Univ., Italy
Volume :
13
Issue :
1
fYear :
1998
fDate :
3/1/1998 12:00:00 AM
Firstpage :
90
Lastpage :
95
Abstract :
The concept of capability chart, traditionally related to the synchronous machines, has been extended to the whole generator-transformer unit, and has proven to be an effective tool in planning and design activities: different solutions can be compared in terms of active and reactive powers injected by the generating unit into the high-voltage busbar. The operation of the unit in points belonging to the capability chart requires to suitably choose the set-points of the unit controls: a control law is proposed which requires minimum changes to the usual control structures, and does not need new measurements. Numerous tests on a typical generating unit highlight the effectiveness of the capability chart as a planning tool, and the features of the proposed control law
Keywords :
busbars; machine control; planning; power transformers; reactive power; synchronous generators; active powers injection; capability chart; control structures; design activities; generator-transformer units; high-voltage busbar; planning activities; reactive powers injection; synchronous machines; unit control set-points; HVDC transmission; Manufacturing; Power & Energy Society; Power generation; Power system planning; Printing; Reactive power; Synchronous generators; Synchronous machines; Testing;
fLanguage :
English
Journal_Title :
Energy Conversion, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8969
Type :
jour
DOI :
10.1109/60.658209
Filename :
658209
Link To Document :
بازگشت