DocumentCode
1309084
Title
Field experience with high-frequency ballasts
Author
Abesamis, Raul S. ; Black, Paul ; Kessel, Jeffrey
Author_Institution
Dept. of Planning & Facilities Maintenance, California Univ., Berkeley, CA, USA
Volume
26
Issue
5
fYear
1990
Firstpage
810
Lastpage
811
Abstract
The Energy Conservation Office of the University of California at Berkeley has installed over 35000 high-frequency ballasts, produced by three manufacturers, in the period from 1986 to the present. The quantities of defective ballasts that are returned to manufacturers for replacement are used to estimate the failure rate of these ballasts under field conditions. It is concluded that careful selection of high-frequency ballasts will result in 20-30% energy savings and reliable quiet flicker-free operation. They provide a rapid payback when specified for new construction or when used as the replacement for failed magnetic ballasts. Depending on operating hours and the cost of electricity, the payback may be acceptable even when high-frequency ballasts are used to replace operating energy-efficient magnetic ballasts (in conjunction with cleaning and lamp replacement). The availability of partial light-output ballasts makes it feasible to fine-tune light levels in spaces that are overlit, gaining a proportional decrease in energy use
Keywords
failure analysis; lamp accessories; reliability; HF; USA; failure rate; field conditions; flicker-free operation; high-frequency ballasts; lamp accessories; light levels; partial light-output ballasts; reliability; Cleaning; Electronic ballasts; Energy conservation; Energy efficiency; Fixtures; Industry Applications Society; Laboratories; Optical sensors; Power system modeling; Virtual manufacturing;
fLanguage
English
Journal_Title
Industry Applications, IEEE Transactions on
Publisher
ieee
ISSN
0093-9994
Type
jour
DOI
10.1109/28.60045
Filename
60045
Link To Document