DocumentCode :
1309891
Title :
Lessons Learned From the Blackout Accident at a Nuclear Power Plant in Taiwan
Author :
Lee, Chien-Hsing ; Chen, Bin-Kwie ; Chen, Nan-Ming ; Liu, Chih-Wen
Author_Institution :
Dept. of Syst. & Naval Mechatron. Eng., Nat. Cheng Kung Univ., Tainan, Taiwan
Volume :
25
Issue :
4
fYear :
2010
Firstpage :
2726
Lastpage :
2733
Abstract :
A power-failure event occurred at the third nuclear power plant (TNPP) in Taiwan in 2001. A chain of events began at 09:36 p.m. on March 16 due to insulation failure associated with flashovers on the 345-kV transmission line. As a result, the 4.16-kV engineered safety features (ESF) buses at the TNPP experienced a loss of power for 2 h and 8 min. This accident was a class 3 emergency (e.g., a class 4 emergency will lead to an overall evacuation of local residents) based on the declared class of emergency in Taiwan. The purpose of this paper is to describe and analyze the chain of events leading to the loss of electrical power. Conclusions on the causes of the outage are drawn and modifications of the system structure are made to improve safety and reliability in a nuclear power plant.
Keywords :
flashover; nuclear power stations; power system reliability; power transmission lines; Taiwan; blackout accident; electrical power; engineered safety features buses; flashovers; insulation failure; nuclear power plant; power failure event; power plant reliability; power plant safety; transmission line; voltage 345 kV; voltage 4.16 kV; Flashover; Generators; Nuclear power generation; Power system reliability; Power transformer insulation; Switches; Voltage control; Insulation flashover; nuclear power plant; power failure; power outage;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/TPWRD.2010.2050340
Filename :
5560703
Link To Document :
بازگشت