Voltage-profile-based approach for developing collection system aggregated models for wind generation resources for grid voltage ride-through studies
Author :
Cheng, Yuan Bing ; Sahni, Manoj ; Conto, Jose ; Huang, Sheng-Huang ; Schmall, John
Author_Institution :
Parsons Brinckerhoff (PB) Power, Dallas, TX, USA
Volume :
5
Issue :
5
fYear :
2011
fDate :
9/1/2011 12:00:00 AM
Firstpage :
332
Lastpage :
346
Abstract :
This paper presents a novel voltage-profile-based approach to develop collection system aggregated models for various WGR facilities to accurately represent their detailed counterparts from a steady state and dynamic voltage response standpoint. A customised automated module developed by the authors is utilised to develop detailed collector system models for WGR facilities accurately representing various aspects of the facility. Short-circuit analysis at the point of common coupling is utilised to obtain the fault-voltage profile at each turbine terminal within the WGR facility. The resulting voltage profile is utilised in conjunction with the under-voltage relay settings associated with the turbine type or types being employed at the facility to identify the number and nature of the groups comprising the aggregated model. Additional short-circuit analysis is performed at breakpoint buses to selectively identify the subnetwork equivalent impedance to represent the aggregated WGR models. The resulting collector system aggregated models are validated from a steady state and dynamic voltage response standpoint by comparison with their detailed counterparts. The paper also demonstrates the robustness of the proposed approach by means of application on different types of WGR facilities currently operational in the ERCOT system. Finally, the effectiveness of the approach is demonstrated performing dynamic simulations utilising the detailed and the aggregated collector system models on the ERCOT dynamic data set and performing comparative analysis on the response with and without the voltage relay models incorporated.
Keywords :
power generation faults; power generation protection; power grids; power system relaying; wind turbines; ERCOT system; breakpoint buses; collection system aggregated models; dynamic voltage response standpoint; fault-voltage profile; grid voltage ride-through; point of common coupling; short-circuit analysis; steady state voltage response; turbine terminal; under-voltage relay settings; voltage-profile-based approach; wind generation resources;
fLanguage :
English
Journal_Title :
Renewable Power Generation, IET
Publisher :
iet
ISSN :
1752-1416
Type :
jour
DOI :
10.1049/iet-rpg.2010.0112
Filename :
6009130
Link To Document :
بازگشت